All LOYTEC products › Configurable automation servers and gateways
LGATE-902

LGATE-902

LGATE-902 is a LOYTEC product in the Configurable automation servers and gateways category. ARINN is LOYTEC's Competence Centre in Scandinavia.

BACnet MS/TPLON/CEA-709BACnet/IPBACnet/SCModbusKNXM-BusOPC UAEnOceanSMIOPC XML-DA

Open in ArinnAgora and add to the quote listOpen datasheet (PDF)L-INX / L-GATE User Manual 8.6L-INX Configurator User Manual 8.6

Description

Universal gateway mapping data points between CEA-709, BACnet, KNX, Modbus and M-Bus; KNX TP1 requires LKNX-300 and M-Bus requires L-MBUS20/80. Configured with L-INX Configurator. Has 1 × RS-485, 1 EXT port and 10,000 data points. BACnet Building Controller (B-BC), BTL-certified.

LOYTEC product text: LGATE-902, EIA709 / BACnet Gateway, 1xTP/FT-10, 1xBACnet MS/TP, 1x EXT Port, 2xEthernet

Courses for this product

Group L can be purchased without a course.

Technical data

Physical connections
Ethernet2 × 100Base-T
RS-4851 × RS-485: BACnet MS/TP or Modbus RTU/ASCII (Master or Slave)
EXT port1 × EXT: M-Bus master EN 13757-3 (needs L-MBUS20/80) or KNX TP1 (needs LKNX-300) or SMI (needs LSMI-800)
CEA-709 TP/FT-101 × TP/FT-10 (either LonMark IP-852 or TP/FT-10)
USB2 × USB-A
KNX TP1KNX TP1 via 1 × EXT (needs LKNX-300); EXT is either M-Bus, KNX TP1 or SMI
M-BusM-Bus master EN 13757-3 via 1 × EXT (needs L-MBUS20/80); EXT is either M-Bus, KNX TP1 or SMI
MP-Busvia USB accessory LMPBUS-804
SMIvia EXT (needs LSMI-800) or USB (needs LSMI-804)
Protocols and wireless
BACnetBACnet/IP, BACnet/SC, BACnet MS/TP (footnote: either BACnet/IP or BACnet MS/TP); BTL certified
ModbusModbus TCP (Master or Slave), Modbus RTU/ASCII (Master or Slave)
OPCOPC XML-DA, OPC UA
KNXnet/IPKNXnet/IP
EnOceanvia USB accessory LENO-80x
WLANvia USB accessory LWLAN-800
Programming
Configured inL-INX Configurator
IoT (Node.js)Node.js
Physical
Display128 × 64 graphic display with backlight
Supply24 V DC / 24 V AC ±10 %
Powertyp. 2.5 W
Dimensions (mm)107 × 100 × 75 mm (L × W × H)
MountingDIN rail (DIN 43880, EN 50022)
Capacity
Total data points10 000
BACnet objects2 000 (analog, binary, multi-state)
BACnet client mappings750
Trend logs256 (13 000 000 entries, ≈ 200 MB)
Schedulers100 BACnet scheduler objects (64 data points per object); 100 LonMark Schedulers
Alarms32 BACnet notification classes; 1 LonMark Alarm Server; 10 alarm logs
Concurrent L-WEB clients32 (simultaneously)

Taken from datasheet Datasheet_LGATE-902.pdf. Hover over a value to see the page. In case of discrepancy, the datasheet applies.

Questions about the product? Call +45 42 62 82 21 or email kontakt@arinn.dk.