LIOB-553
LIOB-553 is a LOYTEC product in the I/O modules category. ARINN is LOYTEC's Competence Centre in Scandinavia.
BACnet/IPL-IOBBACnet/SCOPC UAOPC XML-DA
Open in ArinnAgora and add to the quote listOpen datasheet (PDF)L-IOB I/O Module User Manual 8.6
Description
BACnet I/O module (B-BC, BTL-certified) on BACnet/IP and BACnet/SC with two Ethernet ports, alarming, scheduling and trending. 6 UI, 6 AO, 4 relays 16 A and 1 relay 6 A.
LOYTEC product text: LIOB-553, I/O Module, BACnet IP, B-BC, 6 universal inputs, 4x16A 1x6A relay output, 6x 0-10V output, Ethernet interface
Technical data
| Physical connections | |
|---|---|
| Ethernet | 2 × Ethernet (100Base-T) |
| I/O | |
| L-IOB expansion | LIOB-IP |
| Universal inputs | 6 UI |
| Relay outputs | 4 × 16 A* (* UL: 8 A), 1 × 6 A |
| Analogue outputs | 6 AO |
| Protocols and wireless | |
| BACnet | BACnet/IP, BACnet/SC; BTL certified |
| OPC | OPC XML-DA, OPC UA |
| Physical | |
| Display | 128 × 64 graphic display with backlight |
| Supply | 24 V DC / 24 V AC ±10 % via L‑INX, L‑ROC, L‑POW or LIOB‑A2/A4 via LIOB‑Connect |
| Power | 4.5 W (relays on) |
| Dimensions (mm) | 107 × 100 × 75 mm (L × W × H) |
| Mounting | DIN rail (DIN 43880, EN 50022) |
| Capacity | |
| BACnet objects | 1 per I/O |
| BACnet client mappings | 20 |
| Trend logs | 10 (130 000 entries, ≈ 2 MB) |
| Schedulers | 5 BACnet scheduler objects |
| Alarms | 5 alarm logs; 32 BACnet notification classes |
Taken from datasheet Datasheet_LIOB-55x.pdf. Hover over a value to see the page. In case of discrepancy, the datasheet applies.
Questions about the product? Call +45 42 62 82 21 or email kontakt@arinn.dk.