LROC-102
LROC-102 is a LOYTEC product in the Room controllers category. ARINN is LOYTEC's Competence Centre in Scandinavia.
Open in ArinnAgora and add to the quote listOpen datasheet (PDF)L-ROC User Manual 3.2.8 (L-STUDIO 3)LOYTEC Device User Manual 8.6
If you do not have a trained technician in-house, ARINN will find a Competence Partner for programming and commissioning. ARINN supports the partner with technical advice and access to LOYTEC.
Description
Room controller for up to 16 room segments with event-based IEC 61499, programmed in L-STUDIO. Local inputs and outputs provided by L-IOB modules (up to 24); the unit itself has TP/FT-10, 2 × RS-485 and 2 EXT ports.
LOYTEC product text: LROC-102, Room Controller, 16 room segments, IEC61499, OPC Server, CEA709 FT, LIOB-FT, 2x RS-485, EXT port, IP852, BACnet IP, dual Ethernet, 2x USB
Courses for this product
- LOYTRAIN-LROC-O
Online, free, approx. 17–20 hours in total - LOYTRAIN-LROC-C
3 days, classroom
Group R is sold to customers trained and tested by ARINN or LOYTEC. The course and test required are determined by the task. Contact ARINN.
Technical data
| Physical connections | |
|---|---|
| Ethernet | 2 × 100Base-T |
| RS-485 | 2 × RS-485: BACnet MS/TP or Modbus RTU/ASCII (master or slave) |
| EXT port | 2 × EXT: M-Bus master EN 13757-3 (needs L-MBUS20 or L-MBUS80) or KNX TP1 (needs LKNX-300) or SMI (needs LSMI-800) |
| CEA-709 TP/FT-10 | 1 × TP/FT-10 (LonMark System); router between LonMark IP-852 and TP/FT-10 |
| LIOB-FT | 1 × LIOB-FT |
| LIOB-Connect | 1 × LIOB-Connect |
| USB | 2 × USB-A |
| KNX TP1 | KNX TP1 via EXT port (needs LKNX-300) |
| M-Bus | M-Bus master EN 13757-3 via EXT port (needs L-MBUS20 or L-MBUS80) |
| MP-Bus | via LMPBUS-804 (USB) |
| SMI | via EXT (needs LSMI-800) or USB (needs LSMI-804) |
| I/O | |
| L-IOB expansion | LIOB-Connect, LIOB-FT, LIOB-IP; up to 24 L-IOB I/O Modules |
| Protocols and wireless | |
| BACnet | BACnet/IP, BACnet/SC, BACnet MS/TP (router) |
| Modbus | Modbus TCP (master or slave), Modbus RTU/ASCII (master or slave) |
| OPC | OPC XML-DA, OPC UA |
| KNXnet/IP | KNXnet/IP |
| EnOcean | via LENO-80x (USB) |
| WLAN | via LWLAN-800 (USB) |
| Programming | |
| Programmable | L-STUDIO (IEC 61499) |
| IoT (Node.js) | Node.js |
| Physical | |
| Display | 128 × 64 graphic display with backlight |
| Supply | 24 V DC / V AC SELV ±10 % |
| Power | typ. 2.5 W |
| Dimensions (mm) | 159 × 100 × 75 mm (L × W × H) |
| Mounting | DIN rail (DIN 43880, EN 50022) |
| Capacity | |
| Total data points | 30 000 |
| BACnet objects | 4 000 (analog, binary, multi-state) |
| BACnet client mappings | 5 000 |
| Trend logs | 512 (13 000 000 entries, ≈ 200 MB) |
| Schedulers | 100 BACnet scheduler objects (64 data points per object); 100 LonMark Schedulers |
| Alarms | 32 BACnet notification classes; 1 LonMark Alarm Server; 10 alarm logs |
| Concurrent L-WEB clients | 32 (simultaneously) |
| Room segments | 16 |
Taken from datasheet Datasheet_LROC-102.pdf. Hover over a value to see the page. In case of discrepancy, the datasheet applies.
Expandable with licence
- LROC-SEG8
Adds 8 room segments to an L-ROC room controller. LROC-400 and LROC-402 go from 8 to 16 segments. LROC-401 already has 16. LROC-102 already has 16 and lists the licence in its ordering information; the manual states 8 additional segments per device with the licence.
As per LOYTEC datasheets and manuals. In case of discrepancy, the datasheet applies.
Questions about the product? Call +45 42 62 82 21 or email kontakt@arinn.dk.