All LOYTEC products › Panels and visualisation
LSTAT-800-G3-L3

LSTAT-800-G3-L3

LSTAT-800-G3-L3 is a LOYTEC product in the Panels and visualisation category. ARINN is LOYTEC's Competence Centre in Scandinavia.

Modbus

Open in ArinnAgora and add to the quote listOpen datasheet (PDF)L-STAT User Manual 3.2.8

Description

Room operating unit with LCD for LOYTEC controllers with Modbus, e.g. L-ROC and L-IOB; measures temperature and humidity. Black front, white housing, 8 buttons: temperature and fan up/down, lighting, presence, menu.

LOYTEC product text: LSTAT-800-G3-L3, Room Operator Panel, black front, white enclosure, Modbus, temperature, rel. humidity, ext. switch/NTC, IR receiver, Buttons (L3): temperature up_down/fan up_down/light on_off/occupancy/menu

Technical data

Physical connections
RS-4851 × RS-485: Modbus RTU (master or slave), 1 200–115 200 bit/s (default 57 600 bit/s)
I/O
Universal inputs1 × universal input, either for L-TEMP2 (NTC temperature sensor) or for standard switches and pushbuttons
Digital inputs3 × digital input for standard switches and pushbuttons
Other I/O and sensorsBuilt-in sensors: temperature (range -40–125 °C, resolution 0.1 °C, ±0.5 °C at 5–60 °C), relative humidity (range 0–100 % R.H., resolution 0.1 % R.H., ±2 % R.H. at 25 °C, 20–80 % R.H.; ±3 % R.H. at 25 °C, 0–20 % and 80–100 % R.H.), infrared receiver (NEC protocol); buzzer; 8 × capacitive touch button: temperature up/down, fan up/down, light on/off, occupancy, menu
Protocols and wireless
ModbusModbus RTU (master or slave)
Physical
DisplayLCD display featuring an RGB backlight with adjustable color
Supply24 V DC ±10 %
Powermax. 0.8 W
Dimensions (mm)94.5 × 110 × 19.5 mm (L × W × H)
MountingOnto a flush-mounted box

Taken from datasheet Datasheet_LSTAT-80x.pdf. Hover over a value to see the page. In case of discrepancy, the datasheet applies.

Questions about the product? Call +45 42 62 82 21 or email kontakt@arinn.dk.