All LOYTEC products › Panels and visualisation
LSTAT-800-GX-LX-CU

LSTAT-800-GX-LX-CU

LSTAT-800-GX-LX-CU is a LOYTEC product in the Panels and visualisation category. ARINN is LOYTEC's Competence Centre in Scandinavia.

Open in ArinnAgora and add to the quote listOpen datasheet (PDF)L-STAT User Manual 3.2.8

Description

Customised room operating unit on LSTAT-800 hardware (temperature, humidity) with custom front print. Housing G1 silver, G2 black or G3 white. Minimum 20 units in multiples of 20, typical lead time 12 weeks.

LOYTEC product text: LSTAT-800-Gx-Lx-CU, LSTAT-800 based custom design, Room Operator Panel, minimum order quantity 20 pieces, ordered in multiples of 20, enclosure G1: silver, G2: black, G3: white; custom print Lx, typical lead time 12 weeks

Technical data

Physical connections
RS-4851 × RS-485: Modbus RTU (master or slave), 1 200–115 200 bit/s (default 57 600 bit/s)
I/O
Universal inputs1 × universal input, either for L-TEMP2 (NTC temperature sensor) or for standard switches and pushbuttons
Digital inputs3 × digital input for standard switches and pushbuttons
Other I/O and sensorsBuilt-in sensors: temperature (range -40–125 °C, resolution 0.1 °C, ±0.5 °C at 5–60 °C), relative humidity (range 0–100 % R.H., resolution 0.1 % R.H., ±2 % R.H. at 25 °C, 20–80 % R.H.; ±3 % R.H. at 25 °C, 0–20 % and 80–100 % R.H.), infrared receiver (NEC protocol); buzzer
Protocols and wireless
ModbusModbus RTU (master or slave)
Physical
DisplayLCD display featuring an RGB backlight with adjustable color
Supply24 V DC ±10 %
Powermax. 0.8 W
Dimensions (mm)94.5 × 110 × 19.5 mm (L × W × H)
MountingOnto a flush-mounted box

Taken from datasheet Datasheet_LSTAT-80x.pdf. Hover over a value to see the page. In case of discrepancy, the datasheet applies.