LSTAT-802-GX-LX-CU
LSTAT-802-GX-LX-CU is a LOYTEC product in the Panels and visualisation category. ARINN is LOYTEC's Competence Centre in Scandinavia.
Open in ArinnAgora and add to the quote listOpen datasheet (PDF)L-STAT User Manual 3.2.8
Description
Customised room operating unit on LSTAT-802 hardware (temperature, humidity, occupancy, CO₂) with custom front print. Housing G1 silver, G2 black or G3 white. Minimum 20 pcs in multiples of 20, typical lead time 12 weeks.
LOYTEC product text: LSTAT-802-Gx-Lx-CU, LSTAT-802 based custom design, Room Operator Panel, minimum order quantity 20 pieces, ordered in multiples of 20, enclosure G1: silver, G2: black, G3: white; custom print Lx, typical lead time 12 weeks
Technical data
| Physical connections | |
|---|---|
| RS-485 | 1 × RS-485: Modbus RTU (master or slave), 1 200–115 200 bit/s (default 57 600 bit/s) |
| I/O | |
| Universal inputs | 1 × universal input, either for L-TEMP2 (NTC temperature sensor) or for standard switches and pushbuttons |
| Digital inputs | 3 × digital input for standard switches and pushbuttons |
| Other I/O and sensors | Built-in sensors: temperature (range -40–125 °C, resolution 0.1 °C, ±0.5 °C at 5–60 °C), relative humidity (range 0–100 % R.H., resolution 0.1 % R.H., ±2 % R.H. at 25 °C, 20–80 % R.H.; ±3 % R.H. at 25 °C, 0–20 % and 80–100 % R.H.), occupancy (infrared, max. detection range 5 m, 64 zones), CO₂ (0–2 000 ppm, ±30 ppm or ±3 %), infrared receiver (NEC protocol); buzzer |
| Protocols and wireless | |
| Modbus | Modbus RTU (master or slave) |
| Physical | |
| Display | LCD display featuring an RGB backlight with adjustable color |
| Supply | 24 V DC ±10 % |
| Power | max. 1.8 W |
| Dimensions (mm) | 94.5 × 110 × 19.5 mm (L × W × H) |
| Mounting | Onto a flush-mounted box |
Taken from datasheet Datasheet_LSTAT-80x.pdf. Hover over a value to see the page. In case of discrepancy, the datasheet applies.
Questions about the product? Call +45 42 62 82 21 or email kontakt@arinn.dk.